Difference between revisions of "ArtNet, RDM and Packet Interleaving"

From wiki.openlighting.org

Jump to: navigation, search
(Created page with '== RDM over Artnet == ArtNet nodes behave as pass-through devices for non-discovery RDM data. The normal sequence of RDM commands looks like this: [[Image:ArtNetRDMSeq…')
 
Line 4: Line 4:
  
  
[[Image:ArtNetRDMSequence.png]]
+
[[Image:ArtNetRDMSequence.png|center]]
  
  
 
== The Potential Problem ==
 
== The Potential Problem ==
  
The problem occurs when the RDM device responds with an ACK_OVERFLOW message.  
+
The problem occurs when the RDM device responds with an ACK_OVERFLOW message. From the standard:
 
 
From the standard:
 
  
 
''To receive the remaining data, the controller should continue to send GET_COMMANDS for the same PID. The responder shall send subsequent blocks of data with a response type of RESPONSE_TYPE_ACK_OVERFLOW until the remaining data can fit in a single message. The responder shall set the response type to RESPONSE_TYPE_ACK on the final response message in the sequence, to indicate completion of the data transfer. ''
 
''To receive the remaining data, the controller should continue to send GET_COMMANDS for the same PID. The responder shall send subsequent blocks of data with a response type of RESPONSE_TYPE_ACK_OVERFLOW until the remaining data can fit in a single message. The responder shall set the response type to RESPONSE_TYPE_ACK on the final response message in the sequence, to indicate completion of the data transfer. ''
Line 17: Line 15:
 
Assuming that PID A causes an ACK_OVERFLOW, the sequence now looks like this:
 
Assuming that PID A causes an ACK_OVERFLOW, the sequence now looks like this:
  
[[Image:ArtNetRDMOverflowSequence.png]]
+
[[Image:ArtNetRDMOverflowSequence.png|center]]
  
 
But the standard also states:
 
But the standard also states:
Line 25: Line 23:
 
So any RDM packet interleaved between the two ''GET PID A' commands in the above example will cause the transfer to abort.
 
So any RDM packet interleaved between the two ''GET PID A' commands in the above example will cause the transfer to abort.
  
 +
[[Image:ArtNetRDMOverflowResetSequence.png|center]]
 +
 +
'''Note''': The [http://www.goddarddesign.com/rdm_lab_pack.html Labpack] has a bug where it will not abort the transfer so this continues to work. This is present in version 0x20009
 +
 +
 +
== Possible Solutions ==
 +
 +
There are two cases i) the single controller case ii) the multi-controller case. Nothing in the existing protocol can solve the latter, so it's out of scope for the rest of the discussion.
 +
 +
=== Send a single RDM command at once ===
 +
 +
This is obviously the most reliable but has the drawback of requiring a full round trip between the controller and responder for each message. Testing with a [[Net-Lynx]] showed an average response time of 7ms as seen on the controller when the RTT was 1.3ms. This solution also has the desirable property of not over-running the ArtNet node's buffers.
 +
 +
=== Send multiple packets at once ===
 +
 +
This appears to be what [[DMX Workshop]] does and has the potential to break ack_overflow sequences.
 +
 +
=== Send multiple packets at once and back off when an ACK_OVERFLOW is received ===
 +
 +
Similar to the above, this sends multiple packets at once but stops sending other packets when an ACK_OVERFLOW is received until the sequence completes (or a timeout occurs). This reduces the chance of an aborted transfer, but doesn't eliminate it.
 +
 +
=== Send multiple packets at once, serialize commands expected to generate ACK_OVERFLOWS and back off when an ACK_OVERFLOW is received ===
 +
 +
Of the PIDs described in E1.20, the following have the potential to generate an ACK_OVERFLOW:
 +
 +
* PROXIED_DEVICES
 +
* STATUS_MESSAGES
 +
* SUPPORTED_PARAMETERS
 +
* LANGUAGE_CAPABILITIES
 +
* SLOT_INFO
 +
* DEFAULT_SLOT_VALUE
  
* Note that the [http://www.goddarddesign.com/rdm_lab_pack.html Labpack] has a bug where it will not abort the transfer so this continues to work. This is present in version 0x20009
+
When the Controller sends any of these PIDs it can wait to see if an ACK_OVERFLOW occurs before sending any other RDM commands. Of course this doesn't solve the problem for manufacturer specific PIDs, instead it relies on the back off mechanism above.
  
 
== References ==
 
== References ==

Revision as of 10:43, 6 September 2010

RDM over Artnet

ArtNet nodes behave as pass-through devices for non-discovery RDM data. The normal sequence of RDM commands looks like this:


ArtNetRDMSequence.png


The Potential Problem

The problem occurs when the RDM device responds with an ACK_OVERFLOW message. From the standard:

To receive the remaining data, the controller should continue to send GET_COMMANDS for the same PID. The responder shall send subsequent blocks of data with a response type of RESPONSE_TYPE_ACK_OVERFLOW until the remaining data can fit in a single message. The responder shall set the response type to RESPONSE_TYPE_ACK on the final response message in the sequence, to indicate completion of the data transfer.

Assuming that PID A causes an ACK_OVERFLOW, the sequence now looks like this:

ArtNetRDMOverflowSequence.png

But the standard also states:

The responder shall abort a partial transfer of overflow data for a PID when receiving a command for a different PID before the overflow data transfer is complete. A subsequent command for the overflow PID will result in a new data transfer starting at the beginning of the data set.

So any RDM packet interleaved between the two GET PID A' commands in the above example will cause the transfer to abort.

ArtNetRDMOverflowResetSequence.png

Note: The Labpack has a bug where it will not abort the transfer so this continues to work. This is present in version 0x20009


Possible Solutions

There are two cases i) the single controller case ii) the multi-controller case. Nothing in the existing protocol can solve the latter, so it's out of scope for the rest of the discussion.

Send a single RDM command at once

This is obviously the most reliable but has the drawback of requiring a full round trip between the controller and responder for each message. Testing with a Net-Lynx showed an average response time of 7ms as seen on the controller when the RTT was 1.3ms. This solution also has the desirable property of not over-running the ArtNet node's buffers.

Send multiple packets at once

This appears to be what DMX Workshop does and has the potential to break ack_overflow sequences.

Send multiple packets at once and back off when an ACK_OVERFLOW is received

Similar to the above, this sends multiple packets at once but stops sending other packets when an ACK_OVERFLOW is received until the sequence completes (or a timeout occurs). This reduces the chance of an aborted transfer, but doesn't eliminate it.

Send multiple packets at once, serialize commands expected to generate ACK_OVERFLOWS and back off when an ACK_OVERFLOW is received

Of the PIDs described in E1.20, the following have the potential to generate an ACK_OVERFLOW:

  • PROXIED_DEVICES
  • STATUS_MESSAGES
  • SUPPORTED_PARAMETERS
  • LANGUAGE_CAPABILITIES
  • SLOT_INFO
  • DEFAULT_SLOT_VALUE

When the Controller sends any of these PIDs it can wait to see if an ACK_OVERFLOW occurs before sending any other RDM commands. Of course this doesn't solve the problem for manufacturer specific PIDs, instead it relies on the back off mechanism above.

References